Air & Water Cooled Chillers

TT-54500

These 54 kW water chillers are designed for single or multi-machine applications requiring water temperatures from +10ºC up to +40ºC and ambient temperatures up to +45ºC.

  • Compressor switches on and off automatically to maintain set temperature - circulation pump runs continuously
  • Self-optimising microprocessor controller with digital display of set and actual temperature
  • Electronic control of compressor operating time for extended working life
  • All components in contact with water are stainless steel or bronze
  • Anti-freeze thermostat prevents freezing
  • Automatic or manual refill
  • Automatic level control with pre-warning at low water level Indication lamps for thermal relay of pump and compressor, anti-freeze, low and high pressure and high temperature
  • Castors or rubber feet
Specifications

There are 2 different models available:
TT-54500 Air-cooled standard unit with one-pump system
TT-54500 WK Water-cooled unit with one-pump system
 

  • Cooling Capacity:  Nominal     54 kW
  • Heating Capacity: 12kW
  • Temperature Range: Circulating Water     +10ºC up to +40ºC - Air Temperature     +2ºC up to +45ºC
  • Contents Water Tank: 250 Litres
  • Refrigerating Agent:  R-134a
  • Temperature Control: Self-optimising microprocessor controller with digital display of set and actual temperatures
  • Pump Capacity: at 100 l/min 6 bar. at 200 l/min 4 bar.
  • Compressor: Hermatically sealed
  • Air Volume: 8'000 m3/h (escape at WK)
  • Power Comsumption:  approx. 18 kW
  • Connections:  TO mould     1¼" female thread, FROM mould     1½" female thread, Auto. water refill     3/8" female thread, Drain     1" female thread , Cooling water IN/OUT     1" female thread (only at WK)
  • Dimensions:     L 1'350 x W 1'050 x H 1'950 mm incl. castors
  • Noise level (in 3 m)     65 dBA
  • Weight:    585 kg empty
  • Colour:     Silver grey RAL 7001
Safety Devices
  • Level control provides auto dry run protection
  • Separate mechanical safety thermostat for maximum and minimum temperature
  • Temperature limiter installed in the controller
  • Main switch, automatic cutouts, transformer and main protection switch
  • Audible and visual alarm in case of  failure
Enquire Now

Need help or advice on our products? Enquire Now

/Content/Images/news/chemical-resized.jpg

Latest News

Chemical

In 2018 Tool-Temp installed two TT430 Y units to a chemical company. These units were produced for the customer and are now listed as a machine in our product range. We flew the customer out to our head office in Switzerland to meet with the person in charge of the project, once they had all the requirements the machines went through to production. The units are equipped with three independent heat exchangers. The three-circuit cooling system makes it possible to work with oil below zero degrees. The installed self-optimizing temperature controller MP-988 works with three temperature probe inlets. The reference temperature for the regulation can be the temperature of the product inside the vessel or the oil temperature in the tank of the unit. To avoid any damage of the jacket, the pump pressure can be adjusted to the specifications of the vessel/reactor. The pump revolutions per minute can be adjusted very easily using the frequency inverter. As well as many other features.

Read Article More News