Air & Water Cooled Chillers
TT-108000
These 108 kW water chillers are stationary units for multi machine or very large single consumer applications requiring water temperatures from +10ºC up to +40ºC, at ambient temperatures up to +45ºC.
- Compressor switches on and off automatically to maintain set temperature - circulation pump runs continuously
- Self-optimising microprocessor controller with digital display of set and actual temperature
- Two-pump system - one for internal circuit and one for external circuit ro the consumer
- Electronic control of compressor operating time for extended working life
- All components in contact with water are stainless steel or bronze
- Anti-freeze thermostat prevents freezing
- Automatic or manual refill
- Automatic level control with visible and audible pre-warning at low water level
- Castors or rubber feet
There are 2 different models available:
TT-108000 Air-cooled standard unit with one-pump system
TT-108000 WK Water-cooled unit with one-pump system
- Cooling capacity: Nominal 108 kW
- Temperature Range: Circulating Water +10ºC up to +40ºC - Air Temperature +2ºC up to +45ºC
- Contents water tank: 360 Litres
- Refrigerating agent: R-134a
- Temperature Control: Self-optimising microprocessor controller with digital display of set and actual temperatures
- Pump Capacity: External circuit at 100 l/min 6 bar. at 200 l/min 4 bar. Internal circuit approx. 200 l/min.
- Compressor: Hermatically sealed
- Air Volume: 2 x 8'000 m3/h (escape at WK)
- Power Comsumption: approx. 35 kW
- Connections: TO mould 1½" female thread - FROM mould 2" female thread - Auto. water refill 3/8" female thread - Drain 1" female thread - Cooling water IN/OUT 1" female thread (only at WK)
- Dimensions: L 2'000 x W 1'300 x H 2'090 mm incl. castors
- Noise level: (in 3 m) 70 dBA
- Weight: 1'160 kg empty
- Colour: Silver grey RAL 7001
Model TT-108000 WK is water cooled and needs at least 1,5 bar water pressure
with cooling water(approx.30ºC): approx. 130 l/min. cooling water consumption
with tap water (approx.10-15ºC): approx. 50-75 l/min. cooling water consumption
- Level control provides auto dry run protection
- Separate mechanical safety thermostat for maximum and minimum temperature
- Temperature limiter installed in the controller
- Main switch, automatic cutouts, transformer and main protection switch
- Audible and visual alarm in case of failure